A simple, versatile intermediate-current solution, this KLM/GMT fuse panel includes eight KLM fuse positions (four per side, up to 30A each) and eight GMT fuse positions (four per side, up to 15A each) in just 1 RU. A removable alarm card includes power and alarm LEDs for both feeds. Hardware enables flush or extended mounting in 19″ or 23″ racks.
FEATURES
• 100A input rating per bus (dual feed) in one rack unit
• Large range of output amperages
• Wire-binding output connections accept either bare wire or compression lugs
• Input connections accept two-hole compression lugs
• NEBS approved
Specifications
| Inputs | |
| Voltage & Range | -48VDC, -40V to 60V |
| Max. input load rating | 100A per side |
| Max. total load rating | 100A per side |
| Max. power dissipation at full load | 40W per side @ 4800W full load per side (100Ax48V) |
| Percentage of full load power dissipation | Less than 0.5% |
| Max. input interrupt device | 125A |
| Input terminal studs (with flat washers and KEPS nuts) | Two pairs of #10-32 studs on 5/8 in. centers (3/8 in. socket). Torque nut to 20 in.-lb (2.26 N•m). |
| Input wire size | #4 to #2 AWG (depends on input interrupt device) |
| Dimensions | |
| Nominal, without brackets | Width 17.25 in. (~438 mm) Height 1.75 in. (~44 mm) Depth 8 in. (~203 mm) |